BCI16 BCI18

TRANSFORMER CONTROLLED : BCI16 | BCI18

  • A range of 4-pole, single or 2-bearing transformer controlled generators designed for very high motor starting loads (450 % for up to 7 seconds) where fine voltage regulation is less critical.
  • Engine adaptors to SAE 1, 2, 3, 4, 5 & 6, and coupling discs to SAE 61/2, 71/2, 8, 10 & 111/2, are offered on the BCI versions.
  • Dedicated adaptors for Lister Petter Alpha and TS/TR engine ranges are available on the BCAI & BCLI.
  • Windings are specific to output voltage (single or three phase).
  • Voltages available range up to 480 V.
  • IP23 enclosure protection is standard.

Industrial Class "H" Continuous Ratings (kVA)

    50Hz 60Hz
BCI 16 - 3-phase
BCI 18 - 3-phase
BCAI 16 - 3-phase
BCLI 16 - 3-phase
BCLI 18 - 3-phase
4 pole
4 pole
4 pole
4 pole
4 pole
6.3 - 15.1
17.5 - 30.0
6.3 - 28.5
6.3 - 15.1
17.5 - 25.1
7.8 - 17.5
21.9 - 35.0
7.8 - 33.3
7.8 - 17.5
21.9 - 30.0
BCI 16 - 1-phase
BCI 18 - 1-phase
BCAI 16 - 1-phase
BCLI 16 - 1-phase
BCLI 18 - 1-phase
1 pole
1 pole
1 pole
1 pole
1 pole
4.0 - 9.8
11.5 - 20.0
4.0 - 19.0
4.0 - 9.8
11.5 - 16.5
5.0 - 11.2
4.4 - 23.5
5.0 - 22.3
5.0 - 11.2
14.4 - 20.0
Marine versions of this range are not offered.