STAMFORD AVR Selection

Automatic Voltage Regulator (AVR) & Accessory Selection Tables.

The table below will indicate which AVR accessory is available for, or incorporated into each product range.

5
  MX321 MX341 AS440 SX460 AS480 DM110
5
P0/P1 N N N S S O
UC22 O O O S N O
UC27 O O O S N O
HC4 O O S N N O
HC5 O O S N N O
HC6 S N N N N O
P7 O S N N N O
MV7 S N N N N O
P80 N N N N N S
S = Standard | O = Option | N = Not available
 
AVR features
  MX
321
MX
341
AS
440
SX
460
Transformer
Controlled
Comments/
Restrictions 
 Voltage
Regulation
0.5% 1% 1% 1% 5% With 4%
engine
governing
CSA
Aproval
Yes Yes Yes Yes Yes AVR Feature
 Three Phase
Sensing
Yes No No No No AVR Feature
 
Sensing
Excitation
Limiting
No No No No No AVR Feature
Short Circuit
Current
Limiting
Yes No No No No Additional CT
Required
 Under
Frequency
Protection
Yes Yes Yes Yes No AVR Feature
Load
Acceptance
Feature UFRO
Yes Yes Yes Yes No AVR Feature
 
Add on accessories
  MX
321
MX
341
SX
421
SX
440
SA
465
SX
460
Comments/Restrictions 
Excitation
circuit
breaker
Yes No Yes No No No For isolation of the
excitation system,
standard on the SX421
RFI
suppressor
kit
Yes Yes Yes Yes Yes Yes  
Seperate
voltage
trimmer
Yes Yes Yes Yes Yes Yes For remote mounting
Quadrature
droop kit
(3 phase)
Yes Yes Yes Yes Yes No  
Power factor
controller -
PFC3
Yes Yes Yes Yes Yes No Supplied loose on
BC184 & SA465
Remote
control
interface
Yes Yes Yes Yes Yes Yes For use with power
factor controller
Excitation
loss
module
Yes Yes Yes Yes No Yes Select 12 V or 24 V
Diode failure
detector
Yes Yes Yes Yes No No  
Alternator
protection
module
Yes Yes Yes No No No Select 380 V or 220 V
Frequency
detection
module
Yes Yes Yes No No No Select 12 V or 24 V
Dual AVR
(manual
change over)
Yes No Yes No No No Hard wired spare AVR
Manual
voltage
regulator
Yes Yes No No No No  
Line drop
compensation
Yes Yes Yes Yes No Yes Counters line drop on
long transmission lines
* The excitation circuit breaker supports the overvoltage protection on the MX321 & MA327.
Both functions are facilitated by the excitation circuit breaker on the SX421.

Visit us at the following
exhibitions:

Shipbuilding, Machinery
& Marine Technology

Hamburg, Germany
Stand No. 250, Hall A4
7th – 10th September 2010

Powergen International
Orange County Convention Center,
West Halls, Orlando
Stand No. 3011
14th – 16th December 2010

Middle East Electricity
Dubai International Exhibition Centre, Dubai, UAE
Stand No. 4A10
8th – 10th February 2011

©2010 Cummins Generator Technologies. All Rights Reserved.